Free weekly fire alarm test sheet template

A weekly fire alarm test sheet records each routine test of a building's fire alarm: which call point was used and whether the alarm sounded. Caretakers, office managers and facilities teams fill it in after every test and keep it with the fire log book. This template has one row for each test, with the date and time, the call point, whether the sounders were heard and the panel reset, any fault and who tested.

Download Excel (.xlsx)Download PDF

Free to use and change. No sign up and no email address needed.

What this template is not. This sheet is a record of routine user tests. It does not replace your fire risk assessment, or servicing of the system by a competent fire alarm contractor.

The weekly fire alarm test sheet template

Example rows. The sites, firms and names are made up.
DateTimeCall point testedZoneSounders heardPanel resetMonitoring centre toldFault foundAction takenTested by
05/10/202610:00MCP 1, reception main door1YesYesYesDana W.
12/10/202610:00MCP 2, ground floor rear exit1YesYesYesDana W.
19/10/202610:00MCP 3, stair A first floor2YesYesYesDana W.
26/10/202610:00MCP 4, first floor kitchen2NoYesYesSounder in meeting room 2 silentJob J-20871. Contractor attended 28/10Tom H.
02/11/202610:00MCP 5, stair B first floor2YesYesYesDana W.
09/11/202610:05MCP 6, stair A second floor3YesYesYesDana W.
16/11/202610:00MCP 7, second floor store3YesNoYesPanel showed fault after resetReset again at 10:20, cleared. Told contractorTom H.
23/11/202610:00MCP 8, roof plant deck exit4YesYesYesDana W.

What each column is for

Date
The date of the test.
Time
The time of the test. Testing at the same time each week tells people it is a test.
Call point tested
The number and location of the manual call point used. Use a different one each time.
Zone
The zone shown on the panel when the call point was operated.
Sounders heard
Yes if the alarm could be heard as expected in the areas you checked.
Panel reset
Yes if the panel was silenced and reset, and shows normal.
Monitoring centre told
Yes if you told the alarm receiving centre before and after. Write N/A if the system is not monitored.
Fault found
Anything that did not work as it should.
Action taken
What was done about the fault, and the job reference.
Tested by
The name or initials of whoever made the test.

How to use it

  1. List your call points. Number every manual call point on a plan, so you can work through them in turn.
  2. Warn people first. Tell the building it is a test. If the system is monitored, tell the alarm receiving centre before you start.
  3. Operate one call point. Use the test key on the next call point in your list. Check the alarm sounds and the panel shows the right zone.
  4. Silence and reset. Reset the call point and the panel, and check the panel shows normal. Tell the receiving centre the test is over.
  5. Write it down straight away. Fill in the row and report any fault to your fire alarm contractor the same day.

Use the live version

A weekly test is easy to forget in a busy week. In OmniSchema Operations it is a planned task that shows as overdue until someone does it.

  • Mark a task done and the next due date is worked out for you.
  • An Overdue page shows what is late today, so nothing hides in a filter.
  • On the paid plans the PPM planner raises a job before each visit is due and gives it to the engineer.
  • Engineers complete the visit steps on their phone, even with no signal, and the history keeps who did what.
Start free and install itPreview the PPM by Building kit

OmniSchema Operations has a free plan with no card needed. See pricing.

Questions people ask

How often should a fire alarm be tested?

BS 5839-1, the British Standard code of practice for fire alarm systems in non domestic premises, recommends a test every week by operating a manual call point, using a different call point each time. Check the current edition and your fire risk assessment.

Is weekly fire alarm testing a legal requirement?

In England and Wales, article 17 of the Regulatory Reform (Fire Safety) Order 2005 requires fire safety equipment to be kept in working order. It does not itself set a weekly test. The weekly test comes from BS 5839-1, and your fire risk assessment should say what applies in your building.

Who can carry out the weekly test?

Any member of staff who has been shown how. Servicing and repairs are for a competent fire alarm contractor.

Why use a different call point each week?

So that every call point is proved to work over time, not only the one nearest the panel.

What should I do if the test finds a fault?

Record it, tell your fire alarm contractor the same day, and tell whoever is responsible for fire safety in the building. Note on the sheet when it was put right.