Free emergency lighting log book template

An emergency lighting log book is the record of each test of a building's emergency lights and of any faults found. Building managers, caretakers and contractors fill it in after every test, and fire officers and insurers may ask to see it. This template has one row for each fitting tested, with the date, the kind of test, the result, the fault, the action taken and the date it was cleared.

Download Excel (.xlsx)Download PDF

Free to use and change. No sign up and no email address needed.

What this template is not. This log is a record sheet. It does not replace your fire risk assessment, or testing and repair by a competent contractor.

The emergency lighting log book template

Example rows. The sites, firms and names are made up.
DateTest typeLocationFitting IDResultFault foundAction takenFault cleared onTested by
02/11/2026Function testGround floor, reception exit signEL-G01PassTom H.
02/11/2026Function testGround floor, corridor by WCEL-G02PassTom H.
02/11/2026Function testStair A, ground to firstEL-S01FailDid not lightJob J-20925 raised19/11/2026Tom H.
02/11/2026Function testFirst floor, open plan by column C4EL-101PassTom H.
02/11/2026Function testFirst floor, kitchenEL-102FailCharge light not showingJob J-20925 raised19/11/2026Tom H.
02/11/2026Function testRoof plant deck exitEL-R01PassTom H.
21/11/2026Full durationGround floor, reception exit signEL-G01PassExample Fire and Security
21/11/2026Full durationStair A, ground to firstEL-S01FailWent out before the end of the testBattery to be replaced. Job J-20962Example Fire and Security

What each column is for

Date
The date of the test.
Test type
Function test for a short check that the fitting lights, or Full duration for the long test.
Location
Where the fitting is.
Fitting ID
Your own reference, matching a label on or beside the fitting.
Result
Pass or Fail.
Fault found
What was wrong, such as did not light, dim, or went out early.
Action taken
What was done, and the job reference if a repair was raised.
Fault cleared on
The date the fitting was repaired and tested again.
Tested by
The name or initials of whoever made the test.

How to use it

  1. List your fittings. Walk the escape routes and give every emergency light and lit exit sign an ID. A marked up floor plan helps.
  2. Test at a quiet time. Use the test key switch or the test facility to cut the normal supply to the fittings, then walk round and check each one is lit.
  3. Record every fitting. Write a row for each fitting, pass or fail, so the log shows the whole system was checked.
  4. Restore the supply and check it charges. Switch the supply back on and make sure each fitting's charge light is showing.
  5. Follow up the fails. Raise a repair for each fail, and fill in Fault cleared on when it has been fixed and tested again.

Use the live version

A log book on a shelf cannot tell you a test was missed. In OmniSchema Operations each test is a planned task with a due date.

  • Mark a task done and the next due date is worked out for you.
  • An Overdue page shows what is late today, so nothing hides in a filter.
  • On the paid plans the PPM planner raises a job before each visit is due and gives it to the engineer.
  • Engineers complete the visit steps on their phone, even with no signal, and the history keeps who did what.
Start free and install itPreview the PPM by Building kit

OmniSchema Operations has a free plan with no card needed. See pricing.

Questions people ask

How often should emergency lighting be tested?

The British Standards for emergency lighting, BS 5266-1 and BS EN 50172, recommend a short function test every month and a full duration test every year. Check the current editions and your fire risk assessment for what applies to your building.

What should an emergency lighting log book include?

The date of each test, the kind of test, which fittings were checked, the result, any fault, what was done and when the fault was cleared.

Who can test emergency lighting?

A short function test can be made by a trained member of staff using the test key. The full duration test and any repairs are usually done by a competent contractor.

What is a full duration test?

The fittings are run on their batteries for their full rated time, often three hours, to prove the batteries last. Do it at a time when the building can manage while the batteries recharge afterwards.

How long should I keep the log?

Keep it for as long as the system is in use, and keep it where the fire and rescue service or an insurer can see it on request.