Free PAT testing register template
A PAT testing register lists each portable electrical appliance, the checks and tests made on it, and whether it passed. Electricians, facilities teams and office managers use one to keep track of what has been tested and what is due. This template has one row for each appliance, with its ID, location, class, visual inspection, test readings, result, test date and next due date.
Free to use and change. No sign up and no email address needed.
What this template is not. This register is a record sheet. It does not replace your own risk assessment, and the inspection and testing itself must be done by someone competent to do it.
The PAT testing register template
| Appliance ID | Appliance | Location | Class | Visual inspection | Earth continuity (ohms) | Insulation (megohms) | Result | Test date | Next due | Tested by | Notes |
|---|---|---|---|---|---|---|---|---|---|---|---|
| PA-001 | Kettle, 3kW | First floor kitchen | I | Pass | 0.06 | Over 200 | Pass | 12/11/2026 | 12/11/2027 | Example Electrical | |
| PA-002 | Microwave oven | First floor kitchen | I | Pass | 0.08 | Over 200 | Pass | 12/11/2026 | 12/11/2027 | Example Electrical | |
| PA-003 | Extension lead, 4 gang, 2m | Reception desk | I | Fail | Fail | 12/11/2026 | Example Electrical | Cable sheath cut. Removed and destroyed | |||
| PA-004 | Laptop charger | Desk 14 | II | Pass | N/A | Over 200 | Pass | 12/11/2026 | 12/11/2028 | Example Electrical | |
| PA-005 | Vacuum cleaner | Cleaner's cupboard | II | Pass | N/A | Over 200 | Pass | 12/11/2026 | 12/05/2027 | Example Electrical | Used daily, so checked more often |
| PA-006 | Fan heater, 2kW | Store room | I | Pass | 0.11 | 150 | Pass | 12/11/2026 | 12/11/2027 | Example Electrical | |
| PA-007 | Desk fan | Desk 3 | II | Pass | N/A | Over 200 | Pass | 12/11/2026 | 12/11/2028 | Example Electrical | |
| PA-008 | Floor polisher | Cleaner's cupboard | I | Pass | 0.09 | Over 200 | Pass | 12/11/2026 | 12/05/2027 | Example Electrical | Plug top replaced before test |
What each column is for
- Appliance ID
- Your own reference, matching the label on the appliance.
- Appliance
- What it is, with the make if that helps tell two apart.
- Location
- The room or user it normally belongs to.
- Class
- Class I for earthed equipment or Class II for double insulated equipment.
- Visual inspection
- Pass or Fail for the check of the plug, lead and casing.
- Earth continuity (ohms)
- The reading for Class I equipment. Write N/A for Class II.
- Insulation (megohms)
- The insulation resistance reading from the tester.
- Result
- Pass or Fail overall.
- Test date
- The date it was inspected and tested.
- Next due
- The date you have decided it should be looked at next.
- Tested by
- The name or initials of whoever did the testing.
- Notes
- What failed, what was done, or anything to watch.
How to use it
- Label every appliance. Give each item an ID and stick a label on it. Write a row for each one, including items staff have brought in if you allow them.
- Record the visual inspection first. Most faults are found by looking: a damaged lead, a cracked plug or signs of overheating.
- Add the test readings. Whoever does the testing fills in the readings from the tester, and the overall result.
- Decide the next due date. Base it on the kind of equipment and how and where it is used, not on a fixed rule. Equipment that is moved and used hard needs looking at more often.
- Remove anything that fails. Take failed items out of use at once, label them, and record what happened to them.
Use the live version
A register in a folder does not tell you what is due next month. In OmniSchema Operations each appliance can be an asset with its own dates.
- Each asset keeps its location, serial number and statutory dates in one list your whole team can see.
- The next due date is worked out from the last one, not typed in by hand.
- Import the spreadsheet you already have to get started.
- Add the PPM by Building kit when you want the visits planned from the same assets.
OmniSchema Operations has a free plan with no card needed. See pricing.
Questions people ask
Is PAT testing a legal requirement?
The Electricity at Work Regulations 1989 require electrical equipment to be maintained so that it is safe. They do not say how this must be done or how often. HSE's guidance on maintaining portable electrical equipment says the right approach depends on the kind of equipment and where it is used.
How often should appliances be tested?
There is no fixed interval. HSE's guidance says to base it on risk: the kind of equipment, how it is used and the place it is used in. Record the date you choose in the Next due column and the reason if it is unusual.
What is the difference between Class I and Class II?
Class I equipment relies on an earth connection for safety, so its earth continuity is tested. Class II equipment is double insulated, is marked with a square inside a square, and has no earth to test.
Who can do PAT testing?
Someone competent: they need the right equipment, know how to use it and understand the results. Simple visual checks can be made by trained staff.
What should a PAT testing register include?
An ID for each appliance, what and where it is, its class, the visual inspection result, the test readings, the overall result, the date and when it is next due.
Related templates
All free templates · Certificate tracking: Gas safety, EICR, fire and lighting certificates, with expiry reminders